Key Specs

Rating Range
30 - 3000 A
30 - 3000 A
Transfer Type
Open Transition (CS), Delayed Transition (CSD), Closed Transition (CSCT)
Open Transition (CS), Delayed Transition (CSD), Closed Transition (CSCT)
Switch Type
Contactor
Contactor

Features At A Glance

Displaying 1-6 of 4

Cat

Product Feature

        
  • Voltage and frequency sensing of both sources and load
  •     
  • USB port to upload/download settings
  •     
  • Available Bluetooth connection and enhanced communication capabilities
  •     
  • Password protection color touchscreen HMI
  •     
  • Integrated help button and menu
  •     
  • Five programmed packages and IO
  •     
  • Contact wear monitoring including real-time status and predicted contact end-of-life (30-1200A only)
  •     
  • Fast controller response to outage recovery and fast switching (<50ms)
Cat

Control Panel

        
  •     
  •     
  • TruOne L4 - color touchscreen HMI compatible with Ekip Connect software, with standard programmable functions and IO, and fast controller response to outage recovery and fast switching (<50ms).
Cat

Functions

        
  • High current protection and alarm
  •     
  • Wide 200-480V range with auto-configuration of system settings for 30-1200A range
  •     
  • High time-based withstand and closing ratings (WCR)
  •     
  • Short-time withstand ratings in every frame (CS, CSD, and CSCT models)
Cat

Standards

        
  •     
  •     
  • UL 1008, NFPA 70, 99, 101 and 110
  •     
  •     
  •     
  • NEMA ICS 10
  •     
  •     
  •     
  • cUL
  •     
  •     
  •     
  • Conducted and radiated emissions - CISPR 11:2009, Class A
  •     
  •     
  •     
  • ESD immunity test - IEC/EN 61000-4-2 Class B
  •     
  •     
  •     
  • Radiated RF, electromagnetic field immunity test - IEC/EN 61000-4-3 10 V/m
  •     
  •     
  •     
  • Electrical fast, transient/burst immunity test - IEC/EN 61000-4-4
  •     
  •     
  •     
  • Surge immunity test - IEC/EN 61000-4-5 0.5 to 2 kV
  •     
  •     
  •     
  • Conducted immunity test - IEC/EN 61000-4-6
  •     
  •     
  •     
  • Voltage dips and interruption immunity - IEC/EN 61000-4-11
  •     
  •     
  •     
  • Harmonic voltage immunity test - IEC/EN 6100-4-13

Product Specifications for Cat® CS Series

Rating Range 30 - 3000 A 30 - 3000 A
Transfer Type Open Transition (CS), Delayed Transition (CSD), Closed Transition (CSCT) Open Transition (CS), Delayed Transition (CSD), Closed Transition (CSCT)
Switch Type Contactor Contactor
Product nodes UL: 30-200 A, 260-1200 A, 1600-3000 A UL: 30-200 A, 260-1200 A, 1600-3000 A
Rated Voltage and Frequency 200-480VAC, 50/60 Hz 200-480VAC, 50/60 Hz
Phase system Single and Three Single and Three
Number of poles 2, 3 and 4 2, 3 and 4
Neutral configuration Solid neutral, Switched neutral, (Optional) Overlapping neutral Solid neutral, Switched neutral, (Optional) Overlapping neutral
Product type Open transition (I-II), Delayed Transition (I-O-II), Closed transition (I-O-II) 1600-3000A only Open transition (I-II), Delayed Transition (I-O-II), Closed transition (I-O-II) 1600-3000A only

Cat® CS Series Standard Equipment

Control

  • Color touchscreen
  • Voltage and frequency settings: Pick up and Drop out
  • Time Delay Settings: Override momentary, Transfer, Generator stop, Center-OFF (Delayed Transition Type), Pre-transfer, Post-transfer, Elevator Pre-signal, Elevator Post-signal, and Load shead.
  • Source failure detections: No Voltage, Under/Over Voltage, Phase missing, Voltage unbalance, Invalid frequency, and Incorrect phase sequence

Additional Features

  • LED indications for ATS, S1 and S2 status
  • Programmable digital inputs/outputs
  • Auto config (voltage, frequency, phase system)
  • Source priority (Source 1/2, No priority)
  • Manual re-transfer
  • In-phase monitor (synchro check)
  • Genset exercising: on-load, off-load
  • In-built power meter module
  • Load shedding
  • Real time clock
  • Event log
  • Predictive maintenance
  • Voltage and current harmonics measuring

Accessories

  • Auxiliary contacts for position indication
  • Digital input/output modules (factory programmed)
  • 12-24 VDC aux supply module for controller
  • Communication modules

Connectivity Capability

  • Modbus RTU (RS-485)
  • Modbus/TCP
  • Profibus DP
  • ProfiNet Yes
  • DeviceNet
  • Ethernet IP

Applications

  • Utility - Utility
  • Utility - Generator

UL short circuit withstand ratings

  • Coordinated breaker WCR
  • Time-based WCR
  • Short-time ratings